臺達VFD-C200系列變頻器故障cd3.1的解決方法

時間:2021-04-27    作者:津信變頻    點擊:

用戶送修一臺臺達C200系列變頻器到上海津信維修服務中心(如下圖1),送電顯示cd3.1(如下圖2所示),不可復位,斷電重新上電后依舊報警,查看C200系列說明書可知,該故障為W相電流偵測異常。






快速判斷故障點的測量方法:
將電流傳感器拆除做單板測試,送電后仍然報警cd3.1,根據電流傳感器線路,將板卡上的G點和1,2,3三個點短接(如下圖3所示)   傳感器型號:6900,(如下圖4所示)




重新做單板送電,此時已經不報警,面板顯示正常,開機至3HZ(如下圖5所示)測驅動波形,上下橋波形均正常。



修復故障:更換該電流傳感器,安裝復原變頻器,開機帶負載測試均正常,故障修復。

         