丹佛斯變頻器VLT2811報警ERR37故障維修經驗

時間:2021-03-25    作者:津信變頻    點擊:
一、故障現象
用戶送修一臺丹佛斯VLT2800變頻器,故障現象為送電后顯示ERR37故障,無法復位。
ERR37故障解釋:內部故障0(控制卡與BMC之間通訊出錯)

二、維修過程
給變頻器送電后,變頻器面板顯示ERR37,根據故障解釋說明,檢查CPU小板反饋至控制卡的信號波形異常,有帶毛刺的尖雜波。測量點為下圖45,47號。


根據這種故障現象,查看相關線路,如下圖:



維修過程如下:
1、讀取芯片25010內部程序正常,排除EEPROM芯片故障;
2、靜態測量PC900周邊電阻正常;
3、更換PC900,故障仍無法復位,排除PC900故障;
4、更換CPU小板,故障仍無法復位,排除CPU故障;
5、更換開關電源部分的電解電容,故障仍無法復位,排除電源故障;
6、更換25010芯片,依舊報警ERR37,查看參數發現顯示的變頻器型號不正常,顯示為“2800 200V—”;
7、更換PC900周邊430歐姆電阻,送電無報警,顯示畫面正常,隔幾分鐘后再送電又報警ERR37;
8、更換PC900周邊1K6歐姆電阻,故障消除;
9、測量45,47點,顯示正常波形圖:



小結:考慮板卡并未腐蝕,分析是由于該電阻自身性能下降導致報ERR37故障,更換之后正常工作;


返回列表