海利普變頻器 SK110-15KW報警E.16故障維修

時間:2023-06-12    作者:津信變頻    點擊:
一、故障現象
變頻器送電后顯示E.16故障,無法復位。E.16故障解釋為輸出短路

二、維修過程

1、給變頻器送上電源后,變頻器面板顯示E.16,檢查變頻器輸出端正常,沒有發現有短路現象;
2、接下來測量IGBT驅動電源+15V以及-5V均正常;
3、測量三相輸出電流檢測電路,查看電流傳感器型號為HXS 50-NP,測量輸入電源只有2.4V,而HXS 50-NP正常工作的輸入電源為5V。可以確定故障點在此。接線圖如下:



4、繼續查看電路板布局,檢查電流互感器供電電源芯片為LM217,該芯片作為5V直流穩壓輸出。測量LM217的輸入電源Vi為12V,輸出電源Vo為2.4V,檢測LM217周邊電阻正常,更換LM217后,輸出電源Vo變為5V,故障復位后未再報警,變頻器顯示正常,機器修復。